All vertical tanks larger than 125 gallons water capacity have additional requirements as specified in sections 6.8.6.3, 6.8.6.4, and 6.8.6.5 in the LP-Gas Code, 2024 edition, these are not new requirements. You also need to see section 5.2.4.4 for details on these requirements. The requirements summary is that these tanks must:
- Be installed on reinforced concrete or steel structural supports according to 5.2.4.4, which requires:
- Self supporting without guy wires,
 - Designed to withstand wind loads at the site,
 - Designed to withstand seismic loads at the site,
 - Designed to withstand hydrostatic test loads the tank may be subjected to, and
 - Wind and seismic loading shall be in accordance with ASCE 7, Minimum Design Loads for Buildings and Other Structures.
 
 - Steel supports shall be protected against fire exposure,
 - Vertical and horizontal tanks in liquid service shall not be manifolded together, and
 - Vertical tanks of different dimensions shall not be manifolded together.
 
See the sections listed for the details.